CDE360 Vector Control AC Drive Chapter 7 Fault Detection and Diagnostics
Accumulative
power-on
time reached
The accumulative power-on time
reaches the setting value.
Clear the record through
the parameter initialization
function.
Accumulative
running time
reached
The accumulative running time
reaches the setting value.
Clear the record through
the parameter initialization
function.
Motor
switchover
during
running
status
Change the selection of the motor
via terminal during running of the
drive.
Perform motor switchover after
the drive stops.
Too large
speed
deviation
The encoder parameters are set
incorrectly.
Set the encoder parameters
properly.
The motor auto-tuning is not
performed.
Perform the motor auto-tuning.
The motor over speed check
parameters are set incorrectly.
Set the motor over speed check
parameters correctly based on
the actual situation.
The encoder parameters are set
incorrectly.
Set the encoder
parameters properly.
The motor auto-tuning is not
performed.
Perform the motor auto-tuning.
The motor over speed check
parameters are set incorrectly.
Set the motor over speed check
parameters correctly based on
the actual situation.
Flux pole
detection
fault
The encoder signal is incorrectly.
UVW signal
feedback
fault
The encoder signal is incorrectly.
The encoder type is incorrect.
Set the encoder type correctly
based on the actual situation.
The cable connection of the
encoder is incorrect.
Eliminate external faults.
Replace the damaged encoder.
Replace the abnormal PG card.