EasyManua.ls Logo

Cardinal 825 - Input;Output Terminal Connections; 825 Source Power Connections

Cardinal 825
156 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
8545-M838-O1 Rev D 825 Installation & Technical
20
INSTALLATION, CONT.
I/O (Input/Output) Terminal Connections 825 Source Power
Refer to the table and Figure No. 16 below to connect each wire to the terminal block.
INPUT/OUTPUT TERMINAL P16 (825 SOURCE POWER)
Terminal
Function
Terminal
Function
1
12v (12VDC from 825)
6
OUT1 (Output 1 @ 100mA MAX.)
2
IN1 (Input 1)
7
OUT2 (Output 2 @ 100mA MAX.)
3
IN2 (Input 2)
8
OUT3 (Output 3 @ 100mA MAX.)
4
IN3 (Input 3)
9
OUT4 (Output 4 @ 100mA MAX.)
5
IN4 (Input 4)
10
GND (Ground)
IMPORTANT!
Install J1 and J2 to allow the 825 to supply (source) 12VDC to a solid-state relay or other
load (100 mA maximum).
Figure No. 16

Table of Contents

Related product manuals