CG Drives & Automation,01-5326-01r5 Functional Description 109
Load Default Values Into Set [243]
With this function three different levels (factory settings)
can be selected for the four parameter sets. When loading
the default settings, all changes made in the software are set
to factory settings. This function also includes selections for
loading default settings to the four different Motor Data
Sets.
Communication information
Copy All Settings to Control Panel
[244]
All the settings can be copied into the control panel
including the motor data. Start commands will be ignored
during copying.
Communication information
243 Default>Set
Default: A
A0
Only the selected parameter set will revert
to its default settings.
B1
C2
D3
ABCD 4
All four parameter sets will revert to the
default settings.
Factory 5
All settings, except [211], [221]-[228],
[261], [3A1] and [923], will revert to the
default settings.
M1 6
Only the selected motor set will revert to
its default settings.
M2 7
M3 8
M4 9
M1234 10
All four motor sets will revert to default
settings.
Modbus Instance no/DeviceNet no: 43023
Profibus slot/index 168/182
EtherCAT and CANopen index (hex) 4bcf
Profinet IO index 19407
Fieldbus format UInt
Modbus format UInt
NOTE: Trip log hour counter and other VIEW ONLY
menus are not regarded as settings and will be
unaffected.
NOTE: If “Factory” is selected, the message “Sure?”
is displayed. Press the + key to display “Yes” and
then Enter to confirm.
NOTE: The parameters in menu “[220] Motor data”,
are not affected by loading defaults when restoring
parameter sets A–D.
244 Copy to CP
Default: No Copy
No Copy 0 Nothing will be copied
Copy 1 Copy all settings
Modbus Instance no/DeviceNet no: 43024
Profibus slot/index 168/183
EtherCAT and CANopen index (hex) 4bd0
Profinet IO index 19408
Fieldbus format UInt
Modbus format UInt
NOTE: The actual value of menu [310] will not be
copied into control panel memory set.