CG Drives & Automation,01-5326-01r5 161
Max Alarm delay [4162]
When the load level without interruption exceeds the alarm
level longer than set “Max Alarm delay” time, an alarm is
activated.
Communication information
Max Pre Alarm [417]
Max Pre AlarmMargin [4171]
With load type Basic [415], used the Max Pre-Alarm Margin
sets the band above the Normal Load, [41B], menu that
does not generate a pre-alarm. With load type Load Curve,
[415], used the Max Pre-Alarm Margin sets the band above
the Load Curve, [41C], that does not generate a pre-alarm.
The Max Pre-Alarm Margin is a percentage of nominal
motor torque.
In case of Load Curve R, the margin is percentage of Load
curve torque at the actual speed.
Communication information
Max Pre Alarm delay [4172]
When the load level without interruption exceeds the alarm
level longer than set “Max PreAlarm delay” time, a warning
is activated.
Communication information
Min Pre Alarm [418]
Min Pre Alarm Margin [4181]
With load type Basic, [415], used the Min Pre-Alarm
Margin sets the band under the Normal Load, [41B], menu
that does not generate a pre-alarm. With load type Load
Curve, [415], used the Min Pre-Alarm Margin sets the band
under the Load Curve, [41C], that does not generate a
pre-alarm. The Min Pre-Alarm Margin is a percentage of
nominal motor torque.
In case of Load Curve R, the margin is percentage of Load
curve torque at the actual speed.
Communication information
4162 MaxAlarmDel
Default: 0.1 s
Range: 0-90 s
Modbus Instance no/DeviceNet no: 43330
Profibus slot/index 169/234
EtherCAT and CANopen index (hex) 4d02
Profinet IO index 19714
Fieldbus format Long, 1=0.1 s
Modbus format EInt
4171 MaxPreAlMar
Default: 10%
Range: 0–400%
Modbus Instance no/DeviceNet no: 43327
Profibus slot/index 169/231
EtherCAT and CANopen index (hex) 4cff
Profinet IO index 19711
Fieldbus format Long, 1=1%
Modbus format EInt
4172 MaxPreAlDel
Default: 0.1 s
Range: 0–90 s
Modbus Instance no/DeviceNet no: 43331
Profibus slot/index 169/235
EtherCAT and CANopen index (hex) 4d03
Profinet IO index 19715
Fieldbus format Long, 1=0.1 s
Modbus format EInt
4181 MinPreAlMar
Default: 10%
Range: 0-400%
Modbus Instance no/DeviceNet no: 43328
Profibus slot/index 169/232
EtherCAT and CANopen index (hex) 4d00
Profinet IO index 19712
Fieldbus format Long, 1=1%
Modbus format EInt