Table 99: Modbus memory map: Status of the digital inputs (Logic state mode)
Status of digital inputs
Variable Address Default value
Status of digital inputs 4E20 -
The variable format is shown in Table 100:
Table 100: Variable format: Status of digital inputs.
Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
0 0 0 0 0 0
Input 2
0: OFF
1: ON
Input 1
0: OFF
1: ON
8.3.9.16.- Digital outputs
Reading the status of the digital outputs. The Function 0x04 is implemented for this variable.
Table 101: Modbus memory map: Status of the digital outputs
Status of the digital outputs
Variable Address Default value
Status of the digital outputs 4E21 -
The variable format is shown in Table 102:
Table 102: Variable format: Status of the digital outputs.
Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
0 0 0 0
Output 4
0: OFF
1: ON
Output 3
0: OFF
1: ON
Output 2
0: OFF
1: ON
Output 1
0: OFF
1: ON
8.3.9.17.- Communications
Table 103: Modbus memory map: Communications
Communications
Configuration variable Address Valid data margin
Default
value
Protocol 2742
0 : Modbus
1: Bacnet
(25)
0
Modbus and BACnet: Peripheral number 2743 1 - 255 1
Modbus: Transmission speed 2744
0: 9600 - 1:19200 - 2: 38400
0
BACnet: Transmission speed 2744 0
Modbus: Parity 2745
0: No parity
1: Odd parity
2: Even parity
0
Modbus: Data bits 2746 0 : 8 bits
(26)
0
Modbus: Stop bits 2747
0 : 1 stop bit
1: 2 stop bits
0
BACnet: Device ID 2EE0- 2EE1 0- 999999 -
BAcnet: MAC 2EE2 0- 255 2
(25)
Not available for model CVM-C11-ITF-IN-ETH-ICT2.
(26)
This parameter cannot be modified.