Table 95: Variable format: Status of the digital outputs.
Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
0 0 0 0 0 0 0
Output 1
0: OFF
1: ON
7.3.9.15. Communications (Models CVM-E3-MINI-xxx)
Table 96: Modbus memory map: Communications
Communications
Configuration variable Address Valid data margin
Default 
value
Protocol 2742
0 : Modbus
1: Bacnet
0
Modbus and BACnet: Peripheral number 2743 0 - 255 1
Modbus : Baud rate 2744
0: 9600 - 1:19200 - 2: 38400
(15) 
 
- 3: 57600
(15)
 - 4: 115200 
(15)
1
Modbus : Parity 2745
0: No parity
1: Odd parity
2: Even parity
0
Modbus : Data bits 2746
0 : 8 bits
1: 7 bits
0
Modbus : Stop bits 2747
0 : 1 stop bit
1: 2 stop bits
0
BACnet: Device ID 2EE0- 2EE1 0- 99999 1
BAcnet: MAC 2EE2 0- 127 2
BAcnet: Baud rate 2744
0: 9600 - 1:19200 - 2: 38400
(15) 
 
- 3: 57600
(15)
 - 4: 115200 
(15)
1
(15)
 Available on devices with software version v2.xx.
7.3.9.16. Password configuration
These variables allow you to lock or unlock access to the programming menu, and also allow you to 
change the password code. The password code may only be changed through this command.
The device does not need you to enter the old password in order for it to record the new one; it records 
the new one directly without any verification.
Table 97: Modbus memory map: Password configuration
Password
Configuration variable Address  Valid data margin Default value
Password value
(16)
2B70 0 - 9999  1234
Lock-Unlock 2B71
0: Unlock
1: Lock
0
(16)
 The password value is read and written in hexadecimal.
102
CVM-E3-MINI
Instruction Manual