InteliDrive DCU Industrial 3.4.0 Global Guide
109
Comms settings
Setpoint group
Communication
Settings
Related FW 3.4.0
Range [units] [ENABLE, DISABLE]
Default value ENABLE
Force value
Alternative config
Step [-]
Comm object 24399 Related applications AS, SS
Description
The parameter switches the address for a 5th ID-DCU Industrial display, the fifth ID-DCU Industrial display
occupies a modem address if ENABLE is set. ENABLE is a default value.
5thRemPan
6 back to List of setpoints
Setpoint group
Communication
Settings
Related FW 3.4.0
Range [units] [32C, 8C]
Default value 32C
Force value
Alternative config
Step [-]
Comm object 24499 Related applications AS, SS
Description
Inter-controller, IG-IB, IB-NT CAN2 bus speed selection.
32C: High speed CAN (250 kBd) applicable with up to 32 controllers, CAN bus limited up to 200 meters.
8C: Low speed CAN (50 kBd) applicable with up to 8 controllers, CAN bus limited up to 900 meters.
Note: Low speed CAN2 bus use for long distance connection only. Set all connected controllers to the
same speed. Other units IG-IB, IB-NT detect CAN bus speed automatically.
Note: If the controller is connected to IB-NT, set the mode to 8C - verified stable communication speed.
CAN Bus Mode
6 back to List of setpoints