InteliDrive DCU Industrial 3.4.0 Global Guide
116
Setpoint group Engine params Related FW 3.4.0
Range [units] 0.0 .. 10.0 [Bar]
Default value 10,0
Force value Alternative
config
Step 0.1
Comm object 9681 Related applications AS, SS
Description
Oil pressure limit when controller stops cranking = one of the engine running indications.
To activate this function any Analog input must be configured to Analog logical input Oil press.
Note: Step, Range and dimension depend on corresponding Analog input sensor characteristic.
Starting POil
6 back to List of setpoints
Setpoint group Engine params Related FW 3.4.0
Range [units] 0.0 .. 10.0 [Bar]
Default value 10,0
Force value
Alternative config
Step 0.1
Comm object 10138 Related applications AS
Description
Coolant pressure limit = one of the engine running indications. To activate this function any Analog input
must be configured to Analog logical input Coolant press.
Note: PRP only
Note: Step, Range and dimension depend on corresponding Analog input sensor characteristic.
StartPCoolant
6 back to List of setpoints