InteliDrive DCU Industrial 3.4.0 Global Guide
130
Setpoint group Engine protect Related FW 3.4.0
Range [units] 0 .. Nominal RPM [RPM]
Default value 500
Force value
Alternative config
Step 1
Comm object 10139 Related applications AS, SS
Description
Binary output Ready to load is closed if RPM > MinLoadSpeed and engine is in Running state. Use this
output to enable/disable connecting of engine load. MinLoadSpeed is a condition to close CLOSE LOAD
(PAGE 1) when panel I/0 button is used to connect load to engine.
MinLoadSpeed
6 back to List of setpoints
Setpoint group Engine protect Related FW 3.4.0
Range [units] Batt <V.. 40.0 [V]
Default value 30.0
Force value
Alternative config
Step 0.1
Comm object 9587 Related applications AS, SS
Description
Warning level for battery over voltage.
Batt > V
6 back to List of setpoints
Setpoint group Engine protect Related FW 3.4.0
Range [units] 8.0 .. Batt >V [V]
Default value 8.0
Force value
Alternative config
Step 0.1
Comm object 8387 Related applications AS, SS
Description
Warning level for low battery voltage.
Batt < V
6 back to List of setpoints