EasyManua.ls Logo

ComAp InteliDrive DCU Industrial - Page 129

ComAp InteliDrive DCU Industrial
350 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
InteliDrive DCU Industrial 3.4.0 Global Guide
129
Setpoint group Engine protect Related FW 3.4.0
Range [units] 0 .. 60 [s]
Default value 0
Force value Alternative
config
Step 1
Comm object 10571 Related applications AS, SS
Description
Delay for Force block protection activation after binary input Force Block 3 is opened. Protection
deactivation is without delay. Protection is activated/deactivated independent on engine running or not
running state.
ForceBlockDel3
6 back to List of setpoints
Setpoint group Engine protect Related FW 3.4.0
Range [units] 0 .. 200 [%]
Default value 110
Force value
Alternative config
Step 1% of Nominal RPM (page 104)
Comm object 8263 Related applications AS, SS
Description
Threshold for engine overspeed protection.
Overspeed
6 back to List of setpoints
Setpoint group Engine protect Related FW 3.4.0
Range [units] 0 .. Starting RPM (page 115) [RPM]
Default value 30
Force value
Alternative config
Step 1
Comm object 8260 Related applications AS, SS
Description
Underspeed alarm is activated when engine is running and actual RPM is below the UnderSpeed threshold.
UnderSpeed
6 back to List of setpoints

Table of Contents