InteliDrive DCU Industrial 3.4.0 Global Guide
128
Setpoint group Engine protect Related FW 3.4.0
Range [units] 0 .. 60 [s]
Default value 0
Force value Alternative
config
Step 1
Comm object 10569 Related applications AS, SS
Description
Delay for Force block protection activation after binary input Force Block 1 is opened. Protection
deactivation is without delay. Protection is activated/deactivated independent on engine running or not
running state.
ForceBlockDel1
6 back to List of setpoints
Setpoint group Engine protect Related FW 3.4.0
Range [units] 0 .. 60 [s]
Default value 0
Force value Alternative
config
Step 1
Comm object 10570 Related applications AS, SS
Description
Delay for Force block protection activation after binary input Force Block 2 is opened. Protection
deactivation is without delay. Protection is activated/deactivated independent on engine running or not
running state.
ForceBlockDel2
6 back to List of setpoints