InteliDrive DCU Industrial 3.4.0 Global Guide
127
Setpoint group Engine protect Related FW 3.4.0
Range [units] 0 .. 60 [s]
Default value 10
Force value Alternative
config
Step 1
Comm object 10133 Related applications AS, SS
Description
Binary input protection is activated when input is closed for longer time than BinInp delay 3. To use this filter,
binary input protection Delay must be configured in DriveConfig to BinInp delay 3.
Note:
BinInp delay x is active only for Binary inputs configured as protection and it is related to protection only.
BinInp delay x does not affect optional logical function of an input.
BinInp Delay 3
6 back to List of setpoints