InteliDrive DCU Industrial 3.4.0 Global Guide
126
Setpoint group Engine protect Related FW 3.4.0
Range [units] 0 .. 60 [s]
Default value 1
Force value
Alternative config
Step 1
Comm object 10131 Related applications AS, SS
Description
Binary input protection is activated when input is closed for longer time than BinInp delay 1. To use this filter,
binary input protection Delay must be configured in DriveConfig to BinInp delay 1. For details see BinInp
Delay 3 (page 127) description.
BinInp Delay 1
6 back to List of setpoints
Setpoint group Engine protect Related FW 3.4.0
Range [units] 0 .. 60 [s]
Default value 5
Force value
Alternative config
Step 1
Comm object 10132 Related applications AS, SS
Description
Binary input protection is activated when input is closed for longer time than BinInp delay 2. To use this filter,
binary input protection Delay must be configured in DriveConfig to BinInp delay 2. For details see BinInp
Delay 3 (page 127) description.
BinInp Delay 2
6 back to List of setpoints