Setpoint group Engine protect Related FW 3.4.0
Range [units] 0 .. 60 [s]
Default value 30
Force value Alternative
config
Step 1
Comm object 10025 Related applications AS, SS
Description
This parameter adjusts delay after engine start when alarms configured as RunOnlyBlkDel3 (i.e. "running
only", group #3) are started to be evaluated. The "running only" alarms are not beeing evaluated while the
engine is not running or then, after start, while the adjusted delay is running.
Note:
Engine running state =
RPM > Starting RPM (page 115) or
Analog input Oil Press > Starting POil (page 116) or
Analog input Coolant Press > StartPCoolant (page 116) (PRP only) or
Active Binary input RunIndication1 or
Active Binary input RunIndication2 or
Active Binary input RunIndication3.
RunOnlyBlkDel3