InteliDrive DCU Industrial 3.4.0 Global Guide
124
Engine protect
Setpoint group Engine protect Related FW 3.4.0
Range [units] 0 .. 600 [s]
Default value 10
Force value
Alternative config
Step 1
Comm object 8264 Related applications AS, SS
Description
The maximum time for which is the binary output Horn closed (horn, buzzer will sound). If it is requested to
sound hound until alarm is cleared, set the parameter to zero.
Horn Timeout
6 back to List of setpoints
Setpoint group Engine protect Related FW 3.4.0
Range [units] 0 .. 60 [s]
Default value 10
Force value
Alternative config
Step 1
Comm object 10023 Related applications AS, SS
Description
This parameter adjusts delay after engine start when alarms configured as RunOnlyBlkDel1 (i.e. "running
only", group #1) are started to be evaluated. The "running only" alarms are not beeing evaluated while the
engine is not running or then, after start, while the adjusted delay is running.
For details see drawing, which is part of RunOnlyBlkDel3 (page 125) description.
RunOnlyBlkDel1
6 back to List of setpoints
Setpoint group Engine protect Related FW 3.4.0
Range [units] 0 .. 60 [s]
Default value 20
Force value
Alternative config
Step 1
Comm object 10024 Related applications AS, SS
Description
This parameter adjusts delay after engine start when alarms configured as RunOnlyBlkDel2 (i.e. "running
only", group #2) are started to be evaluated. The "running only" alarms are not beeing evaluated while the
engine is not running or then, after start, while the adjusted delay is running.
For details see drawing, which is part of RunOnlyBlkDel3 (page 125) description.
RunOnlyBlkDel2
6 back to List of setpoints