InteliDrive DCU Industrial 3.4.0 Global Guide
123
Setpoint group Engine params Related FW 3.4.0
Range [units] 0.0 .. 100.0 [%]
Default value 50.0
Force value
Alternative config
Step 0.1 % of Requested RPM range.
Comm object 10008 Related applications AS
Description
When FIRE SPEED (PAGE 174) is closed the CLUTCH CONNECT (PAGE 196) opens (this action deactivates
loadsharing mode if it was activated before) and ThrottlePos (page 262) is set to Engine params:
FireAlarmSpeed value.
FireAlarmSpeed
6 back to List of setpoints
Setpoint group Engine params Related FW 3.4.0
Range [units] [ENABLED, DISABLED]
Default value DISABLED
Force value
Alternative config
Step [-]
Comm object 10098 Related applications AS, SS
Description
ENABLED: Speed Request (page 256) is defined by Local Speed (page 123) setpoint that can be
modified by Fast edit function from front panel (4 sec Enter, / ¯, Enter).
DISABLED: Speed Request (page 256)t is changed via SPEED UP (PAGE 179) / SPEED DOWN (PAGE 178)
or via REQUESTED RPM (PAGE 236), see Speed Request (page 256) t charts for (page 257) and (page
257) modes.
EnLocalSpeed
6 back to List of setpoints
Setpoint group Engine params Related FW 3.4.0
Range [units] 0.0 .. 100.0 [%]
Default value 0.0
Force value
Alternative config
Step 0.1
Comm object 9948 Related applications AS, SS
Description
Setpoint specifies Speed Request (page 256) when EnLocalSpeed (page 123) = ENABLED. Setpoint
can be changed as standard setpoint or by Fast edit function: press Enter for 4 sec, / ¯ set value, press
Enter to confirm, see Speed Request (page 256) charts for PRP and AUX / EME / HRB modes.
Local Speed
6 back to List of setpoints