InteliDrive DCU Industrial 3.4.0 Global Guide
174
Related FW 3.4.0 Related applications AS
Comm object 170
Description
If input is active and Logical Analog input Requested RPM is not valid (out of range, sensor fail),
ThrottlePos (page 262) is set to Back Up Speed1 (page 140) value. ThrottlePos (page 262) = 0.0ī%
when analog request is out of range and Binary input Back Up Speed is not active.
Back Up Speed2
6 back to List of LBI
Related FW 3.4.0 Related applications AS
Comm object 171
Description
If input is active and Logical Analog input Requested RPM is not valid (out of range, sensor fail),
ThrottlePos (page 262) is set to Back Up Speed1 (page 140) value. ThrottlePos (page 262) = 0.0ī%
when analog request is out of range and Binary input Back Up Speed is not active.
Back Up Speed3
6 back to List of LBI
Related FW 3.4.0 Related applications AS
Comm object 160
Description
If active, clutch is disconnected and ThrottlePos (page 262) is set to FireAlarmSpeed (page 123), the
ThrottlePos value change is influenced by ramp specified by RQSP Ramp (page 143).
Fire Speed
6 back to List of LBI
Related FW 3.4.0 Related applications AS
Comm object 183
Description
If active closes binary output Clutch Connect ā see CLUTCH CONNECT (PAGE 196).
Rem Clutch
6 back to List of LBI
Related FW 3.4.0 Related applications AS, SS
Comm object 68
Description
OR logical function of all StartBlocking Logical Binary inputs forces controller NotReady state (īi.e. disables
engine start). It is active in LOC (Local) mode as well.
StartBlocking1
6 back to List of LBI