InteliDrive DCU Industrial 3.4.0 Global Guide
140
Setpoint group Load sharing Related FW 3.4.0
Range [units] 0.0 .. 100.0 [%]
Default value 50.0
Force value Alternative
config
Step 0.1
Comm object 10099 Related applications AS
Description
See Load sharing block diagram (page 144) - the setpoint value is used instead of Speed Request
(page 256) in loadsharing state, if BACK UP SPEED1 (PAGE 173) is active and REQUESTED RPM (PAGE 236)
reading via analog input is out of range (sensor fail is detected).
Back Up Speed1
6 back to List of setpoints
Setpoint group Load sharing Related FW 3.4.0
Range [units] 0.0 .. 100.0 [%]
Default value 50.0
Force value Alternative
config
Step 0.1
Comm object 10523 Related applications AS
Description
See Load sharing block diagram (page 144) - the setpoint value is used instead of Speed Request
(page 256) in loadsharing state, if BACK UP SPEED1 (PAGE 173) is active and REQUESTED RPM (PAGE 236)
reading via analog input is out of range (sensor fail is detected).
Back Up Speed2
6 back to List of setpoints