EasyManua.ls Logo

ComAp InteliDrive DCU Industrial - Page 173

ComAp InteliDrive DCU Industrial
350 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
InteliDrive DCU Industrial 3.4.0 Global Guide
173
Related FW 3.4.0 Related applications AS
Comm object 158
Description
External “edge sensitive” request for engine start. Input is inactive in LOC (Local) mode. Adjustable number
of attempts (see setpoints Crank Attempts (page 118), MaxCrank Time (page 117) and CrankFailPause
(page 117)).
Remote Start Blackout Start RemRepStart Panel START button
Input sensitive
Edge
sensitive;
2nd edge
skips Idle
Edge sensitive;
Edge sensitive;
Edge sensitive;
2nd edge skips Idle
Active in MODE SS; AS SS
AS SS; AS
LOC
Inactive in MODE LOC LOC LOC all time active
Number of starting
attempts
1 x
Engine params:
Crank Attempts
Engine
params:
Crank
Attempts
1 x
Engine starting signals
Remote Stop
Panel STOP button
(1 sec holding time for Stop button activation!)
Input sensitive
Edge sensitive;
2nd edge skips Cooling
Edge sensitive;
2nd edge skips Cooling
Active in MODE SS; AS SS; AS
Inactive in MODE LOC -
Engine stopping signals
Note: Crank Attempts (page 118) is not followed if Sd Override is active, crank attempts number is
then unlimited in case of Blackout/RemRep Start.
Blackout Start / RemRepStart
6 back to List of LBI
Related FW 3.4.0 Related applications AS
Comm object 159
Description
If input is active and Logical Analog input Requested RPM is not valid (out of range, sensor fail),
ThrottlePos (page 262) is set to Back Up Speed1 (page 140) value. ThrottlePos (page 262) = 0.0%
when analog request is out of range and Binary input Back Up Speed is not active.
Back Up Speed1
6 back to List of LBI

Table of Contents

Related product manuals