InteliDrive DCU Industrial 3.4.0 Global Guide
118
Setpoint group Engine params Related FW 3.4.0
Range [units] 0 .. 200 [-]
Default value 3
Force value
Alternative config
Step 1
Comm object 8255 Related applications AS, SS
Description
Max number of crank attempts.
CMB, EME: Setting to 0 means unlimited number of starting attempts.
Note: There is one start attempt only in case of panel Start button or REMOTE START (PAGE 171)
activation. Number of Cranking attempts based on this setpoint is accepted when start is activated by
REMREPSTART (PRP ONLY) (PAGE 172) or BLACKOUT START / REMREPSTART (PAGE 173) (AUX, EME
and HRB) only. The setpoint is not followed if Sd Override is active, crank attempts number is then
unlimited in case of Blackout Start.
Together with request of unlimited start attempts was created PRESTARTOVRD (PAGE 181) - activation
means immediate transition from state Prestart to Cranking.
Same function was applied to second push of START button. First press of START button activates state
Prestart, second press of START button skips prestart period.
Crank Attempts
6 back to List of setpoints
Setpoint group Engine params Related FW 3.4.0
Range [units] Starting RPM.. Nominal RPM [RPM]
Default value 500
Force value
Alternative config
Step 1
Comm object 9946 Related applications AS
Description
Default Idle speed (should be the same as Idle speed set with engine ECU).
Idle RPM
6 back to List of setpoints