InteliDrive DCU Industrial 3.4.0 Global Guide
119
Setpoint group Engine params Related FW 3.4.0
Range [units] 0.0 .. 100.0 [%]
Default value 0,0
Force value
Alternative config
Step 0.1
Comm object 10010 Related applications AS
Description
Offset of Idle speed in % of RPM difference between nominal and idle setpoints (Nominal RPM – Idle RPM)
– see Function description details on page 63
Note: 100% of Engine Values: Requested Speed is the range between Engine params: Idle RPM
and Basic setting: Nominal RPM.
Idle Offset
6 back to List of setpoints
Setpoint group Engine params Related FW 3.4.0
Range [units] 0 .. 600 [s]
Default value 10
Force value
Alternative config
Step 1
Comm object 9097 Related applications AS, SS
Description
Idle time delay starts when RPM exceeds Starting RPM.
During the Idle time the IDLE/NOMINAL (PAGE 197) is opened and after then it is closed. IDLE/NOMINAL (PAGE
197) opens during Cooling period (Cooling Time) again.
Idle Time
6 back to List of setpoints
Setpoint group Engine params Related FW 3.4.0
Range [units] 0 .. 600 [s]
Default value 0
Force value
Alternative config
Step 1
Comm object 8780 Related applications AS, SS
Description
This is the time the binary output Prelubrication is active. The controller will activate binary output
Prelubrication for this amount of time, then pause for PrelubrPause, then activate again. This will continue
the entire time the engine is not running. Function is not active in controller OFF mode.
PrelubrTime
6 back to List of setpoints