InteliDrive DCU Industrial 3.4.0 Global Guide
120
Setpoint group Engine params Related FW 3.4.0
Range [units] 1 .. 4000 [min]
Default value 1
Force value
Alternative config
Step 1
Comm object 8781 Related applications AS, SS
Description
Time interval between prelubrication cycles –PrelubrTime (page 119).
Note: To use Prelubrication, configure Binary output Prelubrication at first.
Prelubrication is disabled in controller OFF mode or when PrelubrTime is set to zero.
When engine is running Prelubrication binary output is opened.
Prelubrication starts PrelubrPause after engine stops. Prelubrication starts immediately when:
- controller power supply turns on
- mode changes from OFF to another
- Emergency Stop is released
PrelubrPause
6 back to List of setpoints
Setpoint group Engine params Related FW 3.4.0
Range [units] 0 .. 600 [s]
Default value 60
Force value
Alternative config
Step 1
Comm object 9815 Related applications AS, SS
Description
Under normal conditions the engine must certainly stop within this period. The period starts by issuing stop
command.
Stop Time
6 back to List of setpoints
Setpoint group Engine params Related FW 3.4.0
Range [units] 0 .. 600 [s]
Default value 30
Force value
Alternative config
Step 1
Comm object 8258 Related applications AS, SS
Description
Runtime of unloaded engine to cool down engine before stopping.
Cooling Time
6 back to List of setpoints