Setpoint group Engine params Related FW 3.4.0
Range [units] 0 .. 600 [s]
Default value 120
Force value
Alternative config
Step 1
Comm object 8662 Related applications AS, SS
Description
COOLING PUMP (PAGE 200) is closed when engine starts and opens with AfterCoolTime delay after engine
stopping.
AfterCoolTime
6 back to List of setpoints
Setpoint group Engine params Related FW 3.4.0
Range [units] [ENABLED, CHRGFAIL, DISABLED]
Default value DISABLED
Force value
Alternative config
Step [-]
Comm object 9683 Related applications AS, SS
Description
ENABLED: The D+ terminal is used for both functions “running engine detection and charge fail
detection.
CHRGFAIL: The D+ terminal is used for charge fail detection only
DISABLED: The D+ terminal is not used.
Note: Alternator magnetization current is provided independently from the parameter setting.
D+ function
6 back to List of setpoints