InteliDrive DCU Industrial 3.4.0 Global Guide
200
Related FW 3.4.0 Related applications AS, SS
Comm object 37
Description
Ignition system activation / deactivation during start - stop procedure.
The output becomes active during cranking if RPM > 30, becomes inactive during cranking pause and after
stop of the engine (RPM = 0).
Ignition
6 back to List of LBO
Related FW 3.4.0 Related applications AS, SS
Comm object 264
Description
1 sec (fix) pulse prior to transfer from RUNNING (PAGE 231) to COOLING (PAGE 200) state.
Unload
6 back to List of LBO
Related FW 3.4.0 Related applications AS, SS
Comm object 74
Description
Closes in cooling state, opens after engine stop.
Cooling
6 back to List of LBO
Related FW 3.4.0 Related applications AS, SS
Comm object 22
Description
Closed output opens the fuel solenoid. Adjustable to DIESEL or GAS. See also the Fuel Solenoid (page
122) setpoint description.
Fuel Solenoid
6 back to List of LBO
Related FW 3.4.0 Related applications AS, SS
Comm object 40
Description
The output closes when engine starts and opens AfterCoolTime (page 121) delayed after stop the engine.
Cooling Pump
6 back to List of LBO