InteliDrive DCU Industrial 3.4.0 Global Guide
199
Related FW 3.4.0 Related applications AS, SS
Comm object 36
Description
Periodic prelubrication function see PrelubrTime (page 119) and PrelubrPause (page 120).
Prestart
6 back to List of LBO
Related FW 3.4.0 Related applications AS, SS
Comm object 262
Description
Engine ready for start indication: no start blocking alarm is active. Output is active in LOC (Local) mode as
well (even if cant be started by binary inputs).
Ready To Start
6 back to List of LBO
Related FW 3.4.0 Related applications AS, SS
Comm object 67
Description
Output closes if the engine is in Running state and can be loaded. Opens in Cooling state. Active only if
RPM > MinLoadSpeed (page 130).
Ready To Load
6 back to List of LBO
Related FW 3.4.0 Related applications AS, SS
Comm object 1829
Description
Active when continued operation could result in damage to exhaust system, but actual reason of the alarm
may not be exhaust system related.
RedStopLamp
6 back to List of LBO
Related FW 3.4.0 Related applications AS, SS
Comm object 263
Description
It activates when RPM rises above Starting RPM (page 115) and opens when RPM=0.
Engine Running