InteliDrive DCU Industrial 3.4.0 Global Guide
201
Related FW 3.4.0 Related applications AS, SS
Comm object 81
Description
Indicates correctly running firmware when cycling on/off with 0.5s period.
Watchdog
6 back to List of LBO
Related FW 3.4.0 Related applications SS
Comm object 265
Description
The output is closed/opened with rising edge of REM START/STOP (PAGE 180) (or I/0 front panel button)
when engine is in Running state and engine RPM is over MinLoadSpeed. Output opens when RPM is
below MinLoadSpeed (page 130). Close load can be opened remotely (e.g. from InteliMonitor) when
REMOTE ON/OFF (PAGE 168) is closed.
Not Used
6 back to List of LBO
Related FW 3.4.0 Related applications AS, SS
Comm object 266
Description
The output is closed when Governor Mode (page 105) = DROOP or Governor Mode = BIN.INPUT and
corresponding BI DROOP (PAGE 180) is closed. This logical output (Source) can be configured to
corresponding J1939 output (e.g. Governor Mode in Volvo-IndustrialD12 Aux).
Droop Sw
6 back to List of LBO