InteliDrive DCU Industrial 3.4.0 Global Guide
168
Related FW 3.4.0 Related applications AS, SS
Comm object 152
Description
Binary input for Alarm acknowledge (level sensitive) has the same function as controller front panel button
Fault reset (i.e. the acknowledge function is screen sensitive).
Note: There is separated acknowledge for ECU Alarms – see Binary input ECU FLTRESET (PAGE 179)
Fault Reset
6 back to List of LBI
Related FW 3.4.0 Related applications AS, SS
Comm object 153
Description
Binary input Horn Reset is level sensitive.
Horn Reset
6 back to List of LBI
Related FW 3.4.0 Related applications AS, SS
Comm object 12
Description
Controller is switched to OFF mode if input is closed and back to previous mode after is opened. Input is not
active in LOC (Local) mode. Active binary input Remote OFF is indicated by “L” character in the right upper
corner on ID-DCU Industrial screen.
Note: Remote OFF will switch controller to OFF mode even if the ACCESSLOCK INT (PAGE 163) or
ACCESSLOCK EXT (PAGE 161) is active or Controller mode is password protected.
Remote OFF
6 back to List of LBI
Related FW 3.4.0 Related applications AS, SS
Comm object 14
Description
Controller is switched to HRB mode if closed and back to previous mode if opened. Input is not active in
LOC (Local) mode.
Remote HRB
6 back to List of LBI
Related FW 3.4.0 Related applications AS, SS
Comm object 161
Description
CLOSE LOAD (PAGE 1) is closed/opened depends on the state of Remote On/Off binary input when engine
RPM is over MinLoadSpeed (page 130). Remote On/Off is not active in LOCmode.
Remote On/Off
6 back to List of LBI