InteliDrive DCU Industrial 3.4.0 Global Guide
161
Related FW 3.4.0 Related applications AS, SS
Comm object 150
Description
If the input is closed, following commands received via any external terminal (e.g. from InteliMonitor or from
a remote display) are inactive:
Remote engine start, stop commands
No setpoints can be adjusted
Controller mode (e.g. OFF-RUN) cannot be changed
Fault reset and horn reset commands
All other commands (e.g. change of a Remote Switch state)
It is possible to list Setpoints, Values and History
Binary input functions are without change
Engine can be started, stopped via Binary inputs (e.g. REMOTE START (PAGE 1)) or via front panel
buttons.
Note: When this Access Lock input is active, it is still possible to initiate programming from a remotely
connected DriveConfig.
Note: If you need to lock only some of the external terminals, you can use following inputs:
ACCESSLOCKCOM1 (PAGE 163)
ACCESSLOCKCOM2 (PAGE 164)
ACSLOCKCAN2(1) (PAGE 164)
ACSLOCKCAN2(2) (PAGE 165)
ACSLOCKCAN2(3) (PAGE 165)
ACSLOCKCAN2(4) (PAGE 166)
ACSLOCKCAN2(5) (PAGE 166)
Device Command AccessLock int AccessLock ext LOC (Local) mode
ID-DCU Industrial panel START N Y Y
STOP N Y Y
FLT RES Y Y Y
HORN
RES
Y Y Y
Setpoint
change
N Y Y
Mode
change
N Y Y
ID-DCU Industrial Bin Inputs
Remote
Y Y N
InteliDrive local/remote commands blocking overview
Note: Y = available, N = blocked