InteliDrive DCU Industrial 3.4.0 Global Guide
166
Related FW 3.4.0 Related applications AS, SS
Comm object 797
Description
If the input is closed, following commands received via CAN2 with address #4 (e.g. from InteliMonitor or
from a remote display) are inactive:
Remote engine start, stop commands
No setpoints can be adjusted
Controller mode (e.g. OFF-RUN) cannot be changed
Fault reset and horn reset commands
All other commands (e.g. change of a Remote Switch state)
It is possible to list Setpoints, Values and History
Binary input functions are without change
Engine can be started, stopped via Binary inputs (e.g. REMOTE START (PAGE 1)) or via front panel
buttons.
Note: When this Access Lock input is active, it is still possible to initiate programming from a remotely
connected DriveConfig.
AcsLockCAN2(4)
6 back to List of LBI
Related FW 3.4.0 Related applications AS, SS
Comm object 1056
Description
If the input is closed, following commands received via CAN2 with address #5 (e.g. from InteliMonitor or
from a remote display) are inactive:
Remote engine start, stop commands
No setpoints can be adjusted
Controller mode (e.g. OFF-RUN) cannot be changed
Fault reset and horn reset commands
All other commands (e.g. change of a Remote Switch state)
It is possible to list Setpoints, Values and History
Binary input functions are without change
Engine can be started, stopped via Binary inputs (e.g. REMOTE START (PAGE 1)) or via front panel
buttons.
Note: When this Access Lock input is active, it is still possible to initiate programming from a remotely
connected DriveConfig.
AcsLockCAN2(5)
6 back to List of LBI