InteliDrive DCU Industrial 3.4.0 Global Guide
105
Setpoint group Basic settings Related FW 3.4.0
Range [units] [ISOCHRON, DROOP, BIN.INPUT]
Default value ISOCHRON
Force value
Alternative config
Step [-]
Comm object 10230 Related applications AS, SS
Description
Activates/deactivates the logical binary output Droop Sw, that can be configured as J1939 output to switch
ECU mode.
BIN.INPUT: ISOCH/DROOP mode is switched via BI DROOP (PAGE 180) (DROOP when closed).
Governor Mode
6 back to List of setpoints
Setpoint group Basic settings Related FW 3.4.0
Range [units] [IDLE, NOMINAL, BIN.INPUT]
Default value IDLE
Force value Alternative
config
Step [-]
Comm object 10336 Related applications AS, SS
Description
Activates/deactivates the logical binary output Nominal Sw, that can be configured as J1939 output to
switch ECU.
BIN.INPUT: IDLE/NOMINAL mode is switched via BI IDLE (PAGE 180) (NOMINAL when closed).
Idle/Nominal
6 back to List of setpoints