Setpoint group Basic settings Related FW 3.4.0
Range [units] 1 .. 500 [-]
Default value 120
Force value
Alternative config
Step 1
Comm object 10920 Related applications AS, SS
Description
Number of teeth on the engines flywheel for the pick-up connected to ID-RPU.
RPUîGear Teeth
6 back to List of setpoints
Setpoint group Basic settings Related FW 3.4.0
Range [units] 30 .. 4000 [RPM]
Default value 1500
Force value
Alternative config
Step 1
Comm object 8253 Related applications AS, SS
Description
Nominal engine speed, base for Overspeed protection limit and Speed Request (page 256) percentage
calculation.
Note: Nominal RPM must correspond to 100î% Throttle position in ECU for correct Load sharing
function in AS application.
Nominal RPM
6 back to List of setpoints
Setpoint group Basic settings Related FW 3.4.0
Range [units] [ENABLED, DISABLED, EXTERNAL]
Default value ENABLED
Force value
Alternative config
YES
Step [-]
Comm object 10353 Related applications AS, SS
Description
Alarm list indication ECU Diag disabled is indicated when ECU diagnostics is disabled. The ECU
Diagnostic is controlled by ECU DiagBlck binary input in case of setting to EXTERNAL.
ECU Diag
6 back to List of setpoints