InteliDrive DCU Industrial 3.4.0 Global Guide
171
Related FW 3.4.0 Related applications AS, SS
Comm object 927
Description
If the input is activated, engine shutdown is immediately performed. However, the controller behavior is
slightly different compared to other shutdown alarms:
COOLING PUMP (PAGE 200) and PRELUBRICATION (PAGE 198) are deactivated as well.
This input cannot be overriden with the input Sd override.
Note: Because of safety reasons it is recommended to configure this input as Normally closed and use a
NC switch.
IMPORTANT: This is a software function only. It can be extended by a "hard wired"
emergency stop function, which means disconnecting power supply from the controller
outputs.
EmergencyStop1
6 back to List of LBI
Related FW 3.4.0 Related applications AS, SS
Comm object 928
Description
If the input is activated, engine shutdown is immediately performed. However, the controller behavior is
slightly different compared to other shutdown alarms:
COOLING PUMP (PAGE 200) and PRELUBRICATION (PAGE 198) are deactivated as well.
This input cannot be overriden with the input Sd override.
Note: Because of safety reasons it is recommended to configure this input as Normally closed and use a
NC switch.
IMPORTANT: This is a software function only. It can be extended by a "hard wired"
emergency stop function, which means disconnecting power supply from the controller
outputs.
EmergencyStop2
6 back to List of LBI
Related FW 3.4.0 Related applications AS, SS
Comm object 156
Description
External “edge sensitive” request for engine start. Binary input is active in all AUX, EME, HRB and PRP
modes and inactive in LOC (Local) mode. There is only one start attempt, use REMREPSTART (PRP ONLY)
(PAGE 172) or Blackout Start (AUX, EME and HRB) binary input for repetitive starting procedure using
Crank Attempts (page 118) and CrankFailPause (page 117) until the engine does not start. Unsuccessful
start is recorded to Alarm list and History. The second edge on Binary input Remote Start skips the Idle time
when engine is running in Idle state.
Binary input Remote Start signal is equivalent to ID-DCU Industrial front panel Start button.
Remote Start
6 back to List of LBI