EasyManua.ls Logo

ComAp InteliDrive DCU Industrial - Page 141

ComAp InteliDrive DCU Industrial
350 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
InteliDrive DCU Industrial 3.4.0 Global Guide
141
Setpoint group Load sharing Related FW 3.4.0
Range [units] 0.0 .. 100.0 [%]
Default value 50.0
Force value Alternative
config
Step 0.1
Comm object 10524 Related applications AS
Description
See Load sharing block diagram (page 144) - the setpoint value is used instead of Speed Request
(page 256) in loadsharing state, if BACK UP SPEED1 (PAGE 173) is active and REQUESTED RPM (PAGE 236)
reading via analog input is out of range (sensor fail is detected).
Back Up Speed3
6 back to List of setpoints
Setpoint group Load sharing Related FW 3.4.0
Range [units] 0 .. 600 [s]
Default value 60
Force value
Alternative config
Step 1
Comm object 10102 Related applications AS
Description
Engine clutch start protection. Start fail alarm is activated, if engine running condition is not detected during
MaxClStrPer delay time after CLUTCH CONNECT (PAGE 196) is closed.
MaxClStrtPer
6 back to List of setpoints

Table of Contents

Related product manuals