Setpoint group Act. Calls/SMS Related FW 3.4.0
Range [units] [-]
Default value 0
Force value
Alternative config
Step [-]
Comm object 9599 Related applications AS, SS
Description
Address for channel 3 active call. Each above message type has either phone number or e-mail address
associated with it.
AcallCH3-Addr
6 back to List of setpoints
Setpoint group Act. Calls/SMS Related FW 3.4.0
Range [units] 1 .. 30 [-]
Default value 3
Force value
Alternative config
Step 1
Comm object 24512 Related applications AS, SS
Description
Number of rings prior to open modem connection from PC to controller.
Note: Num Rings AA change is not accepted immediately, but only after controller is switched on or
when modem is connected to controller.
Num Rings AA
6 back to List of setpoints
Setpoint group Act. Calls/SMS Related FW 3.4.0
Range [units] 1 .. 250 [-]
Default value 3
Force value
Alternative config
Step 1
Comm object 24505 Related applications AS, SS
Description
Setpoint specifies number of attempts to open Active call connection when phone line is engaged.
Note: Timeout for connection is 90 sec and after 120 sec controller starts the next attempt. Incoming
calls are blocked when controller is trying to send active call message.