InteliDrive DCU Industrial 3.4.0 Global Guide
157
Setpoint group DetCon20 Related FW 3.4.0
Range [units] 0 .. 255 [-]
Default value 40
Force value
Alternative config
Step 1
Comm object 10304 Related applications AS, SS
Description
Immediate stop limit is knocking value above which DetCon20 binary output TRIP is activated. This causes
engine to shut down if properly wired.
ImmStopLimit
6 back to List of setpoints
Setpoint group DetCon20 Related FW 3.4.0
Range [units] 0.0 .. 100.0 [%/s]
Default value 30.0 %/s
Force value
Alternative config
Step 0.1 %/s
Comm object 10300 Related applications AS, SS
Description
Decrease ramp specifies rate at which is the timing reduction signal (analog output) decreased as soon as
knocking drops below the IgnRedLimit (page 156) (ignition reduction limit).
DecreaseRamp
6 back to List of setpoints
Setpoint group DetCon20 Related FW 3.4.0
Range [units] 0.0 .. 100.0 [%]
Default value 40.0 %
Force value
Alternative config
Step 0.1 %
Comm object 10301 Related applications AS, SS
Description
Timing reduction gain influences rate at which timing reduction signal (analog output) is amplified when
knocking is detected.
TimingRedGain
6 back to List of setpoints