InteliDrive DCU Industrial 3.4.0 Global Guide
156
Setpoint group SCM unit Related FW 3.4.0
Range [units] 0 .. 500 [-]
Default value 0
Force value
Alternative config
Step 1
Comm object 10907 Related applications AS, SS
Description
Conversion ratio (number of pulses for increase by 1) for ID-SCM IMP 2 impulse input / SCM Imp2 value.
Frequency range max. 60 Hz.
Input Setpoint Value
RPM1 FreqRate1 SCM Freq1
RPM2 FreqRate2 SCM Freq2
IMP1 TransferRate1 SCM Imp1
IMP2 TransferRate2 SCM Imp2
Example: To measure actual water flow in liters (or cubic meters) per minute set FreqRate = 10 []
when sensor gives 10 pulses per liter (or cubic meters).
Example: To measure total water consumption in liters (or cubic meters) set TransferRate = 100 []
when sensor gives 100 pulses per 1liter (or cubic meter).
TransferRate2
6 back to List of setpoints
Dedekind
Setpoint group DetCon20 Related FW 3.4.0
Range [units] 0 .. 255 [-]
Default value 10
Force value
Alternative config
Step 1
Comm object 10299 Related applications AS, SS
Description
Ignition reduction limit is knocking value above which the engine is considered to be knocking. If the value is
exceeded, DetCon20 binary output ENGINE KNOCKING is activated and the values assigned to the timing
reduction are altered.
IgnRedLimit
6 back to List of setpoints