InteliDrive DCU Industrial 3.4.0 Global Guide
155
ID-SCM unit
This setpoints are available when the SCM module is configured in DriveConfig / Modules window.
Not possible to use ID-SCM when ID-RPU is used.
Setpoint group SCM unit Related FW 3.4.0
Range [units] 0 .. 500 [-]
Default value 0
Force value
Alternative config
Step 1
Comm object 10902 Related applications AS, SS
Description
Conversion constant (number of pulses for one RPM) for ID-SCM RPM1 frequency input - SCM Freq1
value. Frequency range max. 8 kHz.
FreqRate1
6 back to List of setpoints
Setpoint group SCM unit Related FW 3.4.0
Range [units] 0 .. 500 [-]
Default value 0
Force value
Alternative config
Step 1
Comm object 10903 Related applications AS, SS
Description
Conversion constant (number of pulses for one RPM) for ID-SCM RPM2 frequency input - SCM Freq2
value. Frequency range max. 8 kHz.
FreqRate2
6 back to List of setpoints
Setpoint group SCM unit Related FW 3.4.0
Range [units] 0 .. 500 [-]
Default value 0
Force value
Alternative config
Step 1
Comm object 10906 Related applications AS, SS
Description
Conversion ratio (number of pulses for increase by 1) for ID-SCM IMP 1 impulse input / SCM Imp1 value.
Frequency range max. 60 Hz.
TransferRate1
6 back to List of setpoints

Table of Contents