InteliDrive DCU Industrial 3.4.0 Global Guide
283
This module is compatible with MTU ECU-7 at communication speed 125 kbps when uploaded with firmware
1.2.0 and higher.
The detection of communication speed is indicated by fast flashing of status LED. Once the speed is detected
the module remains set for the speed even when the communication is lost. Renewal of communication speed
detection is done by reset of the module.
Available inputs/outputs
Analog inputs
8 channels
Can be configured as
Resistor three wire input
Current input
Voltage input
Impulse input
1 channel
Can be configured as
Impulse
Impulse/time
RPM
All inputs can be configured to any logical function or protection.
It is possible to connect up to 10 modules to the InteliGen-NT, InteliSys-NT or InteliMains-NT controllers or up
to 4 modules to the ID-DCU.
Inteli AIN8 module is connected to controller CAN1 bus.
Supported sensors
Sensors
User curves
PT100 [°C] (fix)
PT1000 [°C] (fix)
NI100 [°C] (fix)
NI1000 [°C] (fix)
PT100 [°F] (fix)
PT1000 [°F] (fix)
NI100 [°F] (fix)
NI1000 [°F] (fix)
0-250ohm (fix linear)
0-2400ohm (fix linear)
0-10k ohm (fix linear)
+-1V (fix linear)