InteliDrive DCU Industrial 3.4.0 Global Guide
298
Binary outputs
8 channels
Can be configured as:
High side switch
Low side switch
Always all 8 inputs are configured to one type (HSS/LSS) together.
All 8 outputs can be modified to inputs by switch on the PCB (IO 8/8 to IO 16/0).
New function “output state check” can be switched on for all 8 binary outputs.
Note: Theory of binary inputs and outputs (page 347) (Pull Up,Pull Down, High side switch, Low side
switch)
“Output state check” function evaluates in real time the state of binary outputs and adjusted (required) state.
In case of failure (different state of required state and real state) history record and alarm are issued (type of the
alarm is set by “Protection upon module failure” - (no alarm/warning/SD)).
This function is designed for short-circuit or other failure, which causes change of set state of binary output.
Analog outputs
2 channels
Can be configured as:
Voltage 0-10V
Current 0-20mA
PWM (level 5V, with adjustable frequency from 200Hz to 2400Hz, with step 1Hz)
All inputs/outputs can be configured to any logical function or protection.
It is possible to connect up to 12 modules (in configuration 8inputs/8outputs) to the InteliGen-NT, InteliSys-NT
or InteliMains-NT controllers or up to 4 modules to the ID-DCU.
Inteli IO8/8 module is connected to controller CAN1 bus.
Default configuration of module
If the software of the controller supports this module, then you can configure inputs/output to all options.
In case that the software of the controller doesn’t support this module, you can add this module to the
configuration by generic extension (as group of 8 signals).
In this case you cannot define the type of Inputs/outputs, all inputs/outputs are configured as: