InteliDrive DCU Industrial 3.4.0 Global Guide
300
Terminals
BINARY INPUTS 8 binary inputs
BINARY OUTPUT 8 binary outputs (8 binary inputs)
ANALOG OUTPUT 2 analog outputs
CAN CAN1 line
POWER Power supply
BINARY INPUTS LED 8 LEDs for binary input indication
BINARY OUTPUT LED 8 LEDs for binary output indication
CAN LED Tx, Rx Indication transmitted or received data
Status LED LED indication of correct function
Bout LED Indicate binary outputs active (non-active = 16 binary inputs are active)
CAN terminator Terminating CAN resistor (active in position “ON”)
TEST jumper Upgrade of sw Upgrade of sw
AT-LINK Connector for AT-LINK
Address and DIP switches setting
Configuration as Inteli IO8/8
CAN address for binary inputs is determined by DIP switch A, CAN address for binary output and analog
outputs is determined by DIP switch B.
Configuration as Inteli IO16/0
CAN address for binary inputs is determinated by DIP switch A, first group of 8 input has address A, second
group of 8 inputs has address A+1. CAN address of analog outputs is set by DIP switch B.