InteliDrive DCU Industrial 3.4.0 Global Guide
301
In case of setting the CAN address to zero, the appropriate group of signals is deactivated.
Programming Firmware
Firmware upgrade is via AT-link (TTL). For programming is necessary to close jumper TEST.
For programming FlashProg PC tool version 4.2 or higher must be used.
LED indication
Binary input
Each binary input has LED which indicates input signal. LED is shining when input signal is set, and LED is
dark while input signal has other state.
Binary output
Each binary output has LED which indicates output signal. Binary output LED is shining when binary output is
set.
Binary output status LED
When this LED is shining, then module is configured as 8 binary inputs and 8 binary outputs.
When this LED is dark, then the module is configured as 16 binary inputs.
LED at power connector status LED
Led status Description
Dark Fw in module does not work correctly.
Flashing
At least one group of signals (binary inputs, binary outputs, analog outputs) with a non-zero
address does not communicated.
Fast flashing Detection of CAN communication speed
Lights
Power supply is in the range and communication between Inteli IO8/8 and controller properly
works.