InteliDrive DCU Industrial 3.4.0 Global Guide
307
Connectors
CAN CAN1 line
BINARY INPUTS 16 binary inputs
BINARY OUTPUT 8 binary output
RPM1, RPM2 2 frequency inputs
POWER Power supply
INPUTS LDD CAN address
OUTPUT LDD CAN address
Address and jumpers settings
CAN 1 address is setting by following procedure:
Press Address buttons (for INPUTS address and OUTPUT address) during IS-BIN8 power supply on to
switch to addressing mode.
Then repeatedly press or keep pressed address button to adjust required address according to
CONTROLLER configuration.
After setting requested address, release the buttons and wait until the digits blink it indicates write the
changed address to EEPROM memory.
CAN 1 Address
Inputs Output
1. IS-BIN16/8 1 1
2. IS-BIN16/8 3 2
3. IS-BIN16/8 5 3
4. IS-BIN16/8 7 4