InteliDrive DCU Industrial 3.4.0 Global Guide
320
7. IS-AIN8 7
8. IS-AIN8 8
9. IS-AIN8 9
10. IS-AIN8 0
Table 8.4 Table of recommended CAN1 address setting
SW version check
Let suppose IS-AIN8 of SW version 1.4. Shortly press address button. Following sequence appears on the
display: number “1”, one second pause, number “4”, two second pause, number “1”, one second pause, number
“4”, two second pause and finally IS-AIN8 actual address. Error message (e.g. SD BOUT2) appears on
Controller screen when Binary input or output Address x is configured but corresponding unit is not recognized
(no message is received from CAN bus). Check IS configuration and corresponding external IS-AIN8, IS-
BIN8/16 unit address setting.
LED indication
Power LED Address LDD
Lighting Blink Lighting Blink
Power supply and CAN
address are with no
problems
CAN1 address is adjusted
different in IS-AIN8 and in
controller
Displaying current
CAN1 address
Displaying current
SW version
Table 8.5 LED / LDD status
Tx Rx
Lighting Blink Lighting Blink
Any data are transmitted
on the CAN1 line
Data are transmitted on the CAN1
line
Any data are
received on the
CAN1 line
Data are received
on the CAN1 line
Table 8.6 Tx/Rx LED status
Wiring