InteliDrive DCU Industrial 3.4.0 Global Guide
341
Number of analog outputs 8, no galvanic separation
Type of analog outputs (jumper selectable) U 0 to 10VDC ± 1% , max 5 mA
I 0 to 20 mA ± 1% , max 500 Ω
p pwm 1200 Hz, 5V level, max 10 mA
Power supply 8 to 36 VDC
Current consumption 100 ÷ 300 mA at 24 VDC
Communication interface CAN1, with jumper selectable address 1 to 4 Jumper selectable terminating resistor 120 Ω
RS232 interface TTL, firmware upgrade via AT-link.
Operating temperature range - 40°C to +70°C
Analog outputs refreshment Max. 300 ms
Image 8.17 Dimensions of I-AOUT8
All dimensions are in mm.
I-AOUT8 unit can be mounted on DIN rail (35 mm).