InteliDrive DCU Industrial 3.4.0 Global Guide
57
Sensor characteristics ± 20mA works in full ± range
on ID-DCU Industrial AI5 to AI8 only. ID-DCU
Industrial AI1 to AI4 measures 0 to 20 mA range
only.
Default sensor characteristics creates conversion
to ±100%.
Bargraph indicates only positive values 0 to +100%.
Conversion from ± 20mA to +100% request with User sensor
Sensor characteristics ± 20mA works in full ± range on ID-DCU Industrial
AI5 to AI8 only. ID-DCU Industrial AI1 to AI4 measures 0 to 20 mA range
only.
1. Create User sensor as below.
2. Configure user sensor instead default ± 20mA sensor.
3. Configure Bargraph 100% to correspond User sensor.
Bargraph indicates full 0 to 100% range in this case.
1. Create sensor like below.