EasyManuals Logo
Home>Danfoss>Air Compressor>Turbocor TT Series

Danfoss Turbocor TT Series User Manual

Danfoss Turbocor TT Series
294 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #104 background imageLoading...
Page #104 background image
Figure 4-83 Input Terminal Block Removal - TTS/TGS/TTH/TGH Rev. H (Except TTS300/TGS230)
4.11.2.4 3-Phase Main Voltage Input Terminal Block Installation - TTS300/TGS230
Figure 4-84 Input Terminal Block Installation - TTS300/TGS230
1. PlacetheTerminalBlockonthecompressorhousing,securewiththeM5x15fasteners,andtorqueto3
Nm(27in.lb.).
2. PlacetheMylarinsulatorinthecentersectionofTerminalBlock.
3. IncludingtheSoftStartACRingterminalsL1,L2,L3,Securethethree(3)FuseAssemblies(BusBarside)
totheSCRsusingtheM6x16fasteners.Onlyfingertightenatthispoint.
4. Installthethree(3)FuseAssembliestotheTerminalBlockwiththesix(6)fastenersandtorqueto4Nm
(35in.lb.).
5. TorquetheM6x16fastenerfortheBusBarsideofthethree(3)FuseAssembliestotheSCRsto4Nm(35
in.lb.).
Page 104 of 294 - M-SV-001-EN Rev. H 1/23/2023