Bearing Sensor Cable Installation:
1. Ensurethatallconnectorsarecleanandfreeofgreaseandsiliconegel.
2. FortheFrontBearingSensorCable,refertoSteps3-5;fortheRearBearingSensorCable,refertoSteps
6-8.
3. Installthe9-pinconnectorattheFrontBearingSensorFeedthroughandtorquethefastenersto0.5Nm
(0.4ft.lb.;4.4in.lb.).
4. Applyathincoatingofdielectricgreasetotheexteriorofthebearingsensor9-pinconnectorwhereit
meetsthefeedthroughtosealfrommoistureingress.
5. InstallthecabletoJ10ontheBackplane.Ensurethatplugisinsertedincorrectpolarity.Refertothe
locatingkeysontheplugandslotsintheconnector(TheFrontlocatingkeyshouldbeattheleftofthe
J10Backplaneclip.).Gentlysqueezetheconnectorretainerstosnaptheconnectorsinplace.
6. Installthe9-pinconnectorattheRearBearingSensorFeedthroughandtorquethefastenersto0.5Nm
(0.4ft.lb.;4.4in.lb.).
7. InstallthegroundwiretoJ11orJ12ontheBackplane.
8. InstallthecabletoJ9ontheBackplane.Ensurethatplugisinsertedincorrectpolarity.Refertothe
locatingkeysontheplugandslotsintheconnector(TheRearlocatingkeyshouldbeatthetopofthe
J9Backplaneclip.).Gentlysqueezetheconnectorretainerstosnaptheconnectorsinplace.Referto
Section4.30.3BearingSensorVerification.
Figure 4-264 Bearing Cable Orientation
9. InstalltheServiceSideCover.RefertoSection4.1.3.1ServiceSideCoverRemovalandInstallationon
page54.
10. Returnthecompressortonormaloperation.
11. Verifysensorcablefunctionalitybyperformingabearingcalibration.RefertoSection5.3Bearing
Calibrationonpage263.
4.30.5 Bearing Sensor Feedthrough Removal and Installation
ThefollowingprocedurewillcontainthesamestepsforeithertheFrontorRearBearingSensorFeedthrough.
4.30.5.1 Bearing Sensor Feedthrough Removal
1. Isolatecompressorpower.
2. RemovetheServiceSideCover.RefertoSection4.1.3.1ServiceSideCoverRemovalandInstallationon
page54.
3. WaitfortheLEDsontheBackplanetoturnoff.
4. Isolatethecompressorandrecovertherefrigerantaccordingtoindustrystandards.RefertoSection3.1
RefrigerantContainmentonpage41.
5. RemovetheServiceSideCover.RefertoSection4.1.3.1ServiceSideCoverRemovalandInstallationon
page54.
M-SV-001-EN Rev. H-1/23/2023 Page 239 of 294

Table of Contents

Other manuals for Danfoss Turbocor TT Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss Turbocor TT Series and is the answer not in the manual?

Danfoss Turbocor TT Series Specifications

General IconGeneral
BrandDanfoss
ModelTurbocor TT Series
CategoryAir Compressor
LanguageEnglish

Related product manuals