4.18.2.9 SCR Temperature Sensor Installation - TTS300/TGS230
1. CarefullythreadtheSCRTemperatureSensorintotheSCRCoolingManifoldandtorqueto6Nm(53
in.lbs.).
CAUTION
BecarefultonotdamagethewireexitingtheSCRTemperatureSensorwhentightening.
2. CarefullyslidethesensorcableundertheSCRCoolingManifoldfromthedischargesideofthe
compressor
3. ConnecttheSCRTemperatureSensortotheCompressorcontrollerHarness.RefertoFigure4-148SCR
TemperatureSensorConnector-TTS300/TGS230onpage146.
4. InstalltheTerminalBlock.RefertoSection4.11.2.2Specific3-PhaseMainVoltageInputTerminalBlock
Removal-TTS300/TGS230onpage102.
5. Connectthedischargepressure/temperaturesensorconnectorifitwasremoved.
6. ContinuetoSection4.18.2.11SCRTemperatureSensorGeneralInstallation.
4.18.2.10 SCR Temperature Sensor Installation - TTS/TGS/TTH/TGH Rev. F and Earlier (Except TTS300/TGS230)
1. CarefullythreadtheSCRTemperatureSensorintotheSCRCoolingManifoldandtorqueto6Nm(53
in.lbs.).
CAUTION
BecarefultonotdamagethewireexitingtheSCRTemperatureSensorwhentightening.
2. Connectthedischargepressure/temperaturesensorconnectorifitwasremoved.
3. InstalltheSCRTemperatureSensorCableinthesamelocation.ItshouldbeontopoftheSCRCooling
ManifoldandnexttotheInverter.RefertoFigure4-150SCRTemperatureSensorConnector-
TTS/TGS/TTH/TGHRev.FandEarlier(ExceptTTS300/TGS230)onpage147.
4. ConnecttheSCRTemperatureSensorCabletotheCompressorControllerCableHarness.
5. InstalltheCapacitorandDCBusAssemblyandverifytheSCRTemperatureSensorCableisnotpinched.
RefertoSection4.21.4.4DCCapacitorBusBarAssemblyInstallation-TTS/TGS/TTH/TGH(Except
TTS300/TGS230)onpage174.
6. InstalltheTerminalBlockandACBusBars.RefertoSection4.113-PhaseMainVoltageInputTerminal
Blockonpage99.
7. ConnecttheSoftStartACwirestotheACBusBars.
8. ContinuetoSection4.18.2.11SCRTemperatureSensorGeneralInstallation.
4.18.2.11 SCR Temperature Sensor General Installation
1. InstalltheSoftStart.RefertoSection4.14SoftStartonpage113.
2. Installthetopcovers.RefertoSection4.1CompressorCoversonpage52.
3. Returnthecompressortonormaloperation.
4.18.2.12 SCR Temperature Sensor Torque Specifications
Table 4-30 SCR Temperature Sensor Torque Specifications
Description Nm Ft.Lb. In.Lb.
SCRTemperatureSensor(excludesTTH/TGHandRevHcompressors) 6 - 53
Page 148 of 294 - M-SV-001-EN Rev. H 1/23/2023

Table of Contents

Other manuals for Danfoss Turbocor TT Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss Turbocor TT Series and is the answer not in the manual?

Danfoss Turbocor TT Series Specifications

General IconGeneral
BrandDanfoss
ModelTurbocor TT Series
CategoryAir Compressor
LanguageEnglish

Related product manuals