EasyManuals Logo

Danfoss Turbocor TT Series User Manual

Danfoss Turbocor TT Series
294 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #119 background imageLoading...
Page #119 background image
Figure 4-101 Closed-Top Soft Start
5. LifttheSoftStartandturnitover,placingitboard-sideupontheACBusBars.RefertoFigure4-102
SoftStartLift.
Figure 4-102 Soft Start Lift
6. UnplugcableconnectorsJ1,J7,andJ8fromtheSoftStart.RefertoFigure4-103Closed-TopSoftStart
ConnectorRemoval.
Figure 4-103 Closed-Top Soft Start Connector Removal
7. RemovetheSoftStartassemblyandplaceitinasafelocation.
4.14.5 Soft Start Removal (Open-Top)
1. IsolatethecompressorpowerasdescribedinSection1.8ElectricalIsolationonpage22.
2. RemovetheSoftStartTemperatureHarness.RefertoFigure4-104Open-TopSoftStartJ7Connector.
M-SV-001-EN Rev. H-1/23/2023 Page 119 of 294