EasyManua.ls Logo

Danfoss Turbocor TT Series

Danfoss Turbocor TT Series
294 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Figure 4-192 Harness Removal from Inverter
5. Verifytherearenobentorbrokenpinconnectors.
6. UsethesameprocesstodisconnecttheInverterCableHarnessfromtheBackplaneJ6connection.
7. Verifytherearenobentorbrokenpinconnectors.
8. RemovetheInverterCableHarnessgroundconnectionfromtheBackplane.RefertoFigure4-193
HarnessRemovalfromBackplane.
Figure 4-193 Harness Removal from Backplane
9. CutanycabletiessecuringtheInverterCableHarnessandpullthroughthecompressorhousing
passage.
4.22.4.2 Inverter Cable Harness Installation
1. InserttheInverterCableHarnessthroughthecompressorpassagekeepinginmindtheground
connectionendneedstogototheBackplane.
2. AligntheInverterCableHarnesstotheInverterconnectorusingthealignmenttabontheconnector.
RefertoFigure4-194InverterConnectorAlignment.
Figure 4-194 Inverter Connector Alignment
Page 178 of 294 - M-SV-001-EN Rev. H 1/23/2023